NOTE! If data reading is to be compatible with MULTICAL
®
66-CDE, a top module
67-06 needs to be used in MULTICAL
®
601.
Impulse inputs can be used for connecting both electric and water meters. Please,
bear in mind the maximum impulse frequency and correct impulse codes (l/impulse
and Wh/impulse), which are selected in FF and GG configuration.
65 – 66 Input A
67 – 68 Input B
9.2 M-Bus, type 67-00-04/08/20
M-Bus can be connected into a star-shape, ring, or bus line. According to the M-Bus
Master supply, and total cabling resistance, up tpo 250 meters can be connected.
Cable resistance < 29 Ohm
Cable capacity < 180 nF
M-Bus network is connected to clips 24 and
25. The polarity is not important. M-Bus is
supplied with impulse inputs.
NOTE! 67-00-04/08 requires the installation
of top 67-06 module.
9.3 Radio/impulse inputs, type 67-00-0A/0B/25/26
The radio module is used for wireless communication over a licence-free radio
frequency; it is available for both interior and exterior antennas.
Further information on the radio module are given in
Radio technical description (5512-012).
Impulse inputs of this module are identical with
the above mentioned modules.
NOTE! 67-00-0A/0B requires the installation
of top 67-06 module. Type 67-00-21 includes
radio and router functions.